A Guide to Emergency Light Codes and Standards

A Guide to Emergency Light Codes and Standards - Bees Lighting

Imagine the power suddenly fails in a busy office building or a crowded retail store. The immediate, disorienting darkness can cause confusion and panic. In that critical moment, the sole purpose of an emergency light is to cut through the chaos, illuminating the path to safety. These fixtures are unsung heroes of building safety, and their performance is governed by a strict set of codes and standards.

For building owners and facility managers, understanding these requirements is not just about compliance—it's about ensuring the well-being of every person inside. This guide will illuminate the essential codes that make sure your emergency lights are ready for anything.

Shop Emergency Lights ►

The Guiding Light: NFPA 101's Core Requirements

The most important document governing emergency lighting is the NFPA 101®, Life Safety Code®. This standard is the foundation for nearly all local and state fire codes in the U.S. It outlines three core principles for any emergency lighting system:

  1. Where to Place Them: Emergency lights are required in virtually all commercial and public buildings. They must be installed to illuminate all parts of the egress path, including corridors, stairwells, changes in direction, and the areas immediately outside the final exit doors.
  2. How Bright They Must Be: The code mandates that emergency lights provide an average of at least 1.0 foot-candle (fc) of light along the entire walking surface. (A foot-candle is roughly the amount of light from a single candle one foot away). This ensures the path is clearly visible and helps prevent trips and falls.
  3. How Long They Must Last: In the event of a power failure, every emergency light must operate on its own battery power for a minimum of 90 minutes.

For more information about NFPA 101®, visit NFPA.org.

emergency lights placement

Wiring and Workplace Law: NFPA 70 and OSHA

Beyond the placement and performance of the lights, two other sets of regulations are critical:

  1. NFPA 70®, National Electrical Code® (NEC®): While NFPA 101 tells you where to put the lights, the NEC tells your electrician how to install them safely. Article 700 of the NEC provides the rules for the electrical system, ensuring it has a reliable power source and that the wiring is done correctly so the system activates exactly as intended. Learn more about NFPA 70® here: NFPA 70® National Electric Code.
  2. OSHA (Occupational Safety and Health Administration): OSHA regulations are federal law designed to protect employees. For business owners, this means you are legally obligated to provide a safe workplace, which includes ensuring all exit routes are continuously and adequately lit by a reliable emergency lighting system. Failure to do so can result in significant legal and financial penalties.

Guaranteed Performance: The UL 924 Standard

While the NFPA dictates how the system should perform, UL 924 is the standard that governs the product itself. For an emergency light to earn the "UL 924 Listed" mark, it must undergo rigorous testing to prove it is safe, durable, and reliable. Key performance standards include:

  1. Automatic Activation: The fixture must detect a loss of normal power and switch to its battery source automatically within 10 seconds.
  2. Durability: The housing must be built from flame-retardant materials that can withstand the demands of a commercial environment.
  3. Verified Runtime: The product is tested to ensure its battery and lamps can sustain the required light output for the full 90-minute duration.

Keeping the Lights On: Mandatory Testing & Maintenance

A compliant system requires regular maintenance to ensure its readiness. The NFPA mandates a strict testing schedule that building owners are legally required to follow and document.

  1. Monthly "30-Second" Test: Once a month, a 30-second functional test must be performed. This is typically done by pressing the "test" button on the unit to confirm that the battery is connected and the lamps illuminate properly.
  2. Annual "90-Minute" Test: Once a year, the system must undergo a full 90-minute discharge test. This simulates a real-world power outage and verifies that the battery's capacity has not degraded and can last the full required time.

emergency lights testing

A written log of all tests must be kept on-site, as the local fire marshal can ask to see it during an inspection.

Beyond the Basics: When Local Codes Get Stricter

It's crucial to remember that while the NFPA provides a national baseline, some jurisdictions have even stricter requirements. Always check your local regulations. For example:

  • New York City: Mandates that emergency lights produce double the light output (an average of 2.0 fc) and be housed in durable steel.
  • Chicago: Requires all emergency lights to have all-steel housing and powerful lamps of at least 12-watt equivalent.

nyc emergency lights

Shop New York Approved Emergency Lights ►

Shop Chicago Approved Emergency Lights ►

The Bottom Line

A properly installed and maintained emergency lighting system is a fundamental component of building safety. It’s a life-saving system that requires high-quality, compliant products and diligent upkeep. By understanding these codes, you can ensure your facility is not only compliant with the law but is truly prepared to protect its occupants.